Guide
Puddle flange vs thrust flange
A puddle flange stops water. A thrust flange transfers pipe force into the structure. Here is how they differ.
The two look alike, a ring on a pipe cast into concrete, but they do different jobs.
A puddle flange is a water stop. Its plate is sized to lengthen the leak path and is usually 6 to 12 mm thick.
A thrust flange, also called an anchor flange, is structural. It transfers the thrust from internal pressure, at a bend, tee or closed valve, into the wall or a thrust block. Its plate thickness and weld are designed for that load, so it is heavier.
Many tank and chamber penetrations need both functions. If your drawing calls for a thrust or anchor flange, send us the design force or the engineer's detail and we will fabricate to it.